Smoke and carbon monoxide alarms (Scotland): every home must meet the tolerable standard
What owners and landlords of homes in Scotland must install to meet the tolerable standard for fire and carbon monoxide detection, which has applied to every home since 1 February 2022, and how it is enforced for rented homes through the repairing standard.
Scotland's rule on smoke and carbon monoxide alarms is a universal standard for every home, not just rented ones. The Housing (Scotland) Act 1987 (Tolerable Standard) (Extension of Criteria) Order 2019 (SSI 2019/8) added two tests to section 86(1) of the 1987 Act: a house must have satisfactory equipment installed for detecting and giving warning of fire, and for detecting and giving warning of carbon monoxide at a hazardous concentration. They took effect on 1 February 2022.
Private landlords are caught twice. A house must meet the tolerable standard to meet the repairing standard in section 13 of the Housing (Scotland) Act 2006, and the repairing standard is enforced through the First-tier Tribunal. The standard is about houses, so it is the duty for accommodation that people use as their home, such as private lets, flats and shared houses. Hotels, guest houses, hostels and other non-domestic premises have their fire safety governed separately by the Fire (Scotland) Act 2005. If you are unsure which applies to a particular property, ask your council.
- Who is responsible
- The property owner is responsible for meeting the standard (gov.scot)
- Smoke alarms
- Living room or most-used room, plus each hallway and landing on every storey (circulation space)
- Heat alarm
- One in every kitchen
- Type and position
- Ceiling-mounted, and all alarms interlinked (if one sounds, they all do), by wire or by radio
- Open plan
- One alarm if no point is over 7.5 metres from it (heat alarm if kitchen included)
- Carbon monoxide alarm
- Required where a carbon-fuelled appliance, such as a boiler, open fire or wood burner, is in the room
- Specialist alarms
- Extra alarms for deaf or deafblind occupants, or linked to a Telecare system (in addition to standard alarms)
- In force
- 1 February 2022 for every house in Scotland, whatever the tenure
- Who can apply
- Tenant, or a local authority, to the First-tier Tribunal (Housing and Property Chamber) about the repairing standard
- Enforcement order
- Repairing standard enforcement order, allowing at least 21 days for the work
- Offence
- Ignoring the order without reasonable excuse, a fine up to level 3
Fit one alarm in the living room or the room used most, and one in every hallway and landing (circulation space) on each storey.
One alarm is enough if no point in the space is more than 7.5 metres from it; it must be a heat alarm if the kitchen is included.
A carbon monoxide alarm is required where there is a carbon-fuelled appliance such as a boiler, open fire or wood burner in the room. Gas cookers and hobs do not count.
Extra alarms for deaf or deafblind occupants, or linked to a Telecare system, must be fitted in addition to the standard alarms.
A tenant, or a local authority, can apply to the First-tier Tribunal (Housing and Property Chamber) about the repairing standard. The tribunal can make a repairing standard enforcement order, allowing at least 21 days to do the work. A landlord who ignores the order without a reasonable excuse commits an offence, fine up to level 3 (Housing (Scotland) Act 2006, sections 22, 24 and 28).