The Regulatory Reform (Fire Safety) Order 2005 applies in England and Wales. In a building with two or more sets of domestic premises, it applies to the building's structure, external walls and common parts, and to all doors between the flats and the common parts. External walls include doors and windows in them and anything attached to their exterior, such as balconies.
The Order does not name a waking watch, a common alarm or a change of evacuation strategy. It sets duties that a defect can trigger. Guidance from the National Fire Chiefs Council (NFCC) and Homes England, and a Home Office fact sheet, cover interim measures.
Who carries the duties
Where the premises are a workplace, the responsible person is the employer, if the workplace is to any extent under the employer's control. In any other case, including a workplace not under the employer's control, the responsible person is the person who has control of the premises in connection with carrying on a trade, business or other undertaking, whether for profit or not. Where the person in control does not have control in connection with an undertaking, the responsible person is the owner.
The responsible person must ensure that the duties in articles 8 to 22B of the Order, and in regulations made under article 24, are complied with. Where the premises are not a workplace, this applies so far as the duties relate to matters within the responsible person's control. The same duties fall on every other person who has, to any extent, control of the premises, so far as they relate to matters within that person's control. A person with an obligation under a contract or tenancy to maintain or repair the premises, or for their safety, is treated as having control to the extent of that obligation.
A responsible person must take such steps as are reasonably practicable to find out whether any other responsible person shares, or has duties in respect of, the premises. Where two or more responsible persons share, or have duties in respect of, premises, whether temporarily or permanently, each of them must:
- inform the others of their name and a UK address at which they, or someone acting on their behalf, will accept notices and other documents
- inform the others of the part of the premises for which they consider themselves a responsible person, and keep a record of that information
- co-operate with the others so far as is necessary to enable them to comply with the Order
- taking into account the nature of their activities, take all reasonable steps to co-ordinate their measures with the measures the others are taking
- take all reasonable steps to inform the others of the risks to relevant persons arising out of or in connection with their undertaking
Duties a defect can trigger under the Order
Review and record the fire risk assessment
The responsible person must review the fire risk assessment regularly, so as to keep it up to date. A review is particularly needed if there is reason to suspect that the assessment is no longer valid, or if there has been a significant change in the matters it relates to. Where the review shows that changes are required, the responsible person must make them.
The Order does not name a newly found defect as a trigger. A defect that the assessment did not account for is best read as reason to suspect that the assessment is no longer valid.
As soon as practicable after the assessment is made or reviewed, the responsible person must make a record of it. The record must in particular include the findings of the assessment, including the measures that have been or will be taken. It must also include any group of persons identified as especially at risk. The record is required whatever the number of employees.
The responsible person must also make and give effect to arrangements for the effective planning, organisation, control, monitoring and review of the preventive and protective measures. The arrangements must be appropriate to the size of the undertaking and the nature of its activities, and the responsible person must record them.
Evacuation procedures
The responsible person must establish, and where necessary give effect to, appropriate procedures, including safety drills, to be followed in the event of serious and imminent danger to relevant persons. The responsible person must also nominate a sufficient number of competent persons to implement those procedures so far as they relate to the evacuation of relevant persons. A person is competent if they have sufficient training and experience, or knowledge and other qualities, to implement the evacuation procedures.
A change of evacuation strategy is best read as a change to these procedures.
Fire detectors and alarms
Where necessary to safeguard relevant persons, the responsible person must ensure that the premises are, to the extent that it is appropriate, equipped with fire detectors and alarms. The need can arise from the features of the premises, the activity carried on there, any hazard present or any other relevant circumstances. What is appropriate depends on the dimensions and use of the premises, the equipment in them, the properties of any substances likely to be present and the maximum number of people who may be present at any one time.
The Order does not name a common alarm for a block of flats.
Where necessary to safeguard relevant persons, the responsible person must also ensure that the premises, and the facilities, equipment and devices provided, are subject to a suitable system of maintenance. They must be maintained in an efficient state, in efficient working order and in good repair. An installed alarm is best read as within that duty.
Tell residents
In a building with two or more sets of domestic premises, the responsible person must give residents comprehensible and relevant information about the relevant fire safety matters. The relevant matters include the risks to residents that the risk assessment identified and the preventive and protective measures. The responsible person must keep records of them. The Order leaves the times and the form of the information to regulations.
In England, regulation 9 of the Fire Safety (England) Regulations 2022 adds a further duty. It applies to a building that contains two or more sets of domestic premises and has common parts through which residents would need to evacuate in an emergency. The responsible person must:
- display fire safety instructions in a conspicuous part of the building, in a form that residents can reasonably be expected to understand
- include in them the evacuation strategy, how to report a fire to the fire and rescue authority, and any other instruction on what residents must do once a fire has occurred
- give a copy to a new resident as soon as reasonably practicable after the resident moves in, and to all residents within each period of 12 months beginning on 23 January 2023
- after any material change to the instructions, display them again and give residents a copy
The Regulations do not define a material change. A change from stay put to simultaneous evacuation alters the instruction on the evacuation strategy, which is best read as a material change.
Extra duties that depend on the building (England)
The Fire Safety (England) Regulations 2022 and the Fire Safety (Residential Evacuation Plans) (England) Regulations 2025 apply in England only.
Alarm checks in a high-rise residential building
A high-rise residential building has two or more sets of domestic premises and is at least 18 metres above ground level or has at least 7 storeys. Height is measured as Appendix D to Approved Document B sets out, and storeys below ground level are ignored.
In such a building, the responsible person must undertake monthly routine checks of essential fire-fighting equipment. Fire detection and fire alarm systems count as essential fire-fighting equipment only where they are located within the common parts of the building. A common alarm fitted in the common parts as an interim measure is within the checks. A routine check is a check that the equipment is in efficient working order and good repair, in line with industry standard or manufacturer recommendations.
The responsible person must take steps to rectify any fault found. Where a fault cannot be rectified within 24 hours beginning with the time it is identified, the responsible person must, as soon as reasonably practicable:
- report the fault to the local fire and rescue authority by electronic means
- report the rectification to the local fire and rescue authority by electronic means when the fault has been rectified
The responsible person must also make a record of the monthly checks and make it accessible to the residents of the building.
External wall record in a high-rise residential building
The responsible person must prepare a record of the design of the external walls, including details of the materials. The record must include details of the level of risk that the design and materials give rise to, as identified in the fire risk assessment, and any mitigating steps taken in respect of that risk. The responsible person must prepare a revised record if there are any significant changes to the external walls. The record must be provided to the local fire and rescue authority by electronic means.
The Home Office fact sheet on regulation 5 says mitigating steps could include whether a waking watch has been established or a sprinkler system installed. The sheet says it is not guidance.
Fire door checks above 11 metres
In a building that has two or more sets of domestic premises and is above 11 metres in height, the responsible person must check fire doors in communal areas at least every 3 months. The responsible person must use best endeavours to check the fire doors at the entrances of individual flats at least every 12 months, and must keep a record of the steps taken. Where access was not granted, the record must show the steps taken to try to gain access. The checks must include ensuring that the self-closing devices are working.
Building emergency evacuation plan
The 2025 Regulations apply to a building with two or more sets of domestic premises that is at least 18 metres high, has at least 7 storeys, or is more than 11 metres high and has a simultaneous evacuation strategy. A simultaneous evacuation strategy means the responsible person has determined that all persons in the building should leave immediately in the event of a fire. The definition does not exclude a strategy adopted for an interim period. Height is measured as Appendix D to Approved Document B sets out.
In such a building the responsible person must also use reasonable endeavours to identify relevant residents. A relevant resident is a resident whose only or principal residence is in the building and whose ability to evacuate without assistance in a fire is compromised by a cognitive or physical impairment or condition. The responsible person must offer each of them a person-centred fire risk assessment, and must ensure one is carried out for each who requests it.
For a building within the 2025 Regulations, the responsible person must prepare a building emergency evacuation plan, provide a copy to the local fire and rescue authority and, where the building has a secure information box, place a copy in it. The responsible person must review the plan no later than 12 months after it is first prepared, and before the end of every period of 12 months after that. The responsible person must also review it if there is reason to believe it requires amending. If the plan is amended, the responsible person must, as soon as reasonably practicable, provide a copy to the local fire and rescue authority and place one in the secure information box, where the building has one.
Interim measures under NFCC guidance
NFCC says the responsible person, not the fire and rescue service or NFCC, makes the decision to change strategy. It says this is usually done with a competent person's advice and a review of the fire risk assessment.
NFCC says the SEG is only intended to apply to buildings that cannot support a stay put strategy. It says the SEG is intended to be used only after a decision has been taken to change the evacuation strategy temporarily. NFCC says responsible persons and their advisers should understand the decision-making process first, and it points to PAS 9980.
NFCC says interim arrangements range from removing ignition sources to changing from stay put to simultaneous evacuation, supported by a common fire alarm, a waking watch or both. It describes them as the temporary, short-term management of the risk. It says the fourth edition of the SEG aims to end a risk-averse, one-size-fits-all use of on-site staffing where that is disproportionate to the risk.
Common fire alarm
The SEG sets out what NFCC calls a clear expectation that responsible persons move quickly to install a common fire alarm. It sets the same expectation for removing or reducing dependence on waking watches as quickly as possible.
Waking watch
NFCC says a waking watch is intended to give sufficient warning of fire to support the evacuation strategy. It says a waking watch is intended for very short periods, while the risk is urgently addressed by remediation or a common fire alarm.
NFCC says it is the duty of the responsible person to ensure that the people on the waking watch are competent to carry out the role. It says training needs to be specific to the building. It says a decision to have on-site staff to manage an evacuation should be informed by a competent person's advice and a holistic review of the fire risk assessment.
Review of the assessment
NFCC says responsible persons for affected buildings should review their fire risk assessment, to ensure the fire safety arrangements, including the interim measures in place, are appropriate. It says the review should be informed by a competent person's advice.
Funding a common alarm in England
Homes England's guidance says the Interim Measures Alarm Fund (IMAF) meets the costs of fire alarm installation to replace or reduce the need for waking watch in residential buildings in England. It does not fund waking watch costs.
Homes England says an application can be made only by what Homes England calls a "Responsible Entity", a responsible person or an authorised representative of a Responsible Entity. Residents and leaseholders cannot apply. The building must be in England, be residential or student accommodation (hotels are not eligible), have 2 or more dwellings, and have a fire risk appraisal of external walls or a fire risk assessment that identifies the need for an interim measures alarm. Homes England says a building that has already received funds from the IMAF or the Waking Watch Replacement Fund, or has an application pending with either, cannot apply.
Homes England says a common fire alarm funded by the IMAF should be designed to meet the recommendations of BS 5839-1 for a Category L5 system. It says the SEG advises considering a specification that allows a later upgrade to a BS 8629 evacuation alert system.
Homes England says responsibility for the fire safety of a building always remains with the responsible person, and that funding does not transfer it.
Apply to the Interim Measures Alarm Fund (IMAF) (opens in a new tab)
What the fire and rescue authority can do
The fire and rescue authority for the area is the enforcing authority, unless another body is named for the premises.
If the enforcing authority is of the opinion that a person has failed to comply with the Order or with regulations made under it, which include the 2022 and 2025 Regulations in England, it may serve an enforcement notice. The notice requires the person to remedy the failure within the period it specifies, which is not less than 28 days from the date of service. It may include directions on the measures to take.
If the enforcing authority is of the opinion that use of the premises involves or will involve a risk to relevant persons so serious that use ought to be prohibited or restricted, it may serve a prohibition notice. The relevant risk includes anything that affects escape from the premises in a fire. A prohibition notice takes effect immediately only if the authority is of the opinion, and says in the notice, that the risk of serious personal injury is or will be imminent. Otherwise it takes effect at the end of the period the notice specifies.
A person served with either notice may appeal to a magistrates' court within 21 days of service. An appeal suspends an enforcement notice. It does not suspend a prohibition notice unless the court so directs.
Offences and penalties
A failure to comply with a duty in articles 8 to 22B or 38 of the Order is an offence only where the failure places one or more relevant persons at risk of death or serious injury in case of fire. The same condition applies to a failure to comply with a requirement or prohibition in regulations made under article 24 of the Order, which include the 2022 and 2025 Regulations in England. Failing to comply with an enforcement notice is also an offence, with no such risk condition. Failing to comply with a prohibition or restriction in a prohibition notice is an offence too.
In England and Wales, the penalty for each of these offences is a fine of any amount on summary conviction, for offences committed on or after 12 March 2015. On conviction on indictment it is a fine, imprisonment for up to 2 years, or both.
Legal basis
Primary legislation and key regulations
Official guidance
NFCC Simultaneous Evacuation Guidance FAQs (opens in a new tab)
nfcc.org.uk · England and Wales
NFCC Simultaneous Evacuation Guidance (high-rise) (opens in a new tab)
nfcc.org.uk · England and Wales
Fire Safety (England) Regulations 2022 guidance (opens in a new tab)
Publication · Home Office · England
Interim Measures Alarm Fund (IMAF) guidance (opens in a new tab)
Homes England · England